Colocation racks explained

Posted on in

A colocation rack gives your servers and network equipment a secure, purpose-built place to run, and you never have to operate the data centre around them. You own and control the hardware. The provider supplies the rack space, power, cooling, physical security and connectivity it depends on.

The rack itself looks simple. Choosing one means getting several constraints right at once. Available U space, cabinet depth, usable power, cooling capacity, cable routes and delivery access all decide whether your equipment fits and runs as planned.

Key takeaways

  • Colocation racks are measured in rack units, or U, with 1U equal to 44.45 mm of vertical mounting space.
  • Full-rack sizes vary from 48U to 42U depending on the provider.
  • Physical rack space and available power are separate constraints. A cabinet can have spare U and no practical capacity for more equipment.
  • A+B power feeds can give you resilient power paths where equipment supports dual supplies.
  • Quarter, half and full racks suit different deployment sizes, and power, connectivity and service requirements matter alongside physical space.
  • Before ordering, confirm equipment dimensions, usable power, cooling requirements, cable entry, delivery access, connectivity and support arrangements.

What is a colocation rack?

A colocation rack is cabinet space rented inside a data centre for servers, switches, storage and other IT equipment the customer owns or controls.

The ownership distinction matters. With colocation the servers stay yours. The provider runs the environment around them: the building, resilient power infrastructure, cooling, physical security and connectivity options.

A server doesn’t turn into a different type of machine when it moves into colocation. It’s the same hardware, just running in rented data centre rack space instead of your own building.

Rack space is sold as part of a cabinet or as a complete rack. Larger deployments use several racks, cages or dedicated areas, and the underlying arrangement stays the same: your IT equipment runs inside infrastructure the colocation provider maintains.

Specifying a rack is therefore not a question of how many servers you have. Their physical dimensions, power draw, airflow, cabling and network requirements all change the space you actually need.

Colocation rack sizes and specifications

Data centre racks use standardised mounting dimensions, so equipment from different manufacturers goes into the same cabinet. A standard mounting format does not make every cabinet interchangeable.

The rack has to fit the equipment physically, supply enough usable power and work with the facility’s cooling and cable-management design.

Rack units and cabinet dimensions

Rack height is measured in rack units, defined as U. One rack unit is 44.45 mm high, and equipment built for standard data centre racks uses a 19-inch mounting format.

A 1U server takes one rack unit. A 2U appliance takes two. A 4U storage chassis takes four.

Full-rack sizes vary from 48U to 42U depending on the provider, so check the exact cabinet height before planning. Do not assume every U in the specification is available for customer equipment. Power distribution units, patching and other rack infrastructure take up part of the cabinet.

Width and depth matter as well.

Cabinets come in different widths and depths to accommodate equipment, cabling and airflow. Deep servers, large switches and storage systems need clearance behind the chassis for power leads, network cables and hot-air exhaust.

Check the dimensions of the equipment itself, not just its U height. A server that fits vertically can still be too deep for the cabinet, or leave too little room for safe cabling.

Installation planning also has to cover the route into the data hall. Doors, lifts, corridors, loading areas and packaging dimensions become constraints well before the equipment reaches the rack.

Power density and cooling

Rack capacity is as much about power as space. Two full-height cabinets can hold completely different workloads: a rack of network equipment draws relatively little power, while dense compute, storage or GPU infrastructure needs substantially more from the same physical footprint. That’s why a rack should be specified in U and in usable power capacity.

Providers describe power in amps or kW, and allocations vary by facility and deployment. Confirm the usable contracted capacity rather than working it out from the nominal rating of the electrical feed.

For resilient deployments, racks can take A and B power feeds following separate paths. Equipment with dual power supplies connects one supply to each feed, so no single power path carries the whole load.

Many data centres arrange racks around hot and cold aisles, so equipment takes cooled air in from one side and pushes heated air out of the other. Others use different designs, such as a pressurised room where warm air is removed above the cabinet.

Whichever approach a facility uses, cooling has to match the load: higher-density equipment needs additional cooling consideration even when the physical rack space is there. This is why spare U doesn’t mean spare capacity. Once the rack hits its usable power or cooling limit, the remaining slots aren’t practically usable for more equipment.

Installation and cable management

Good rack planning leaves room for cables, power distribution and maintenance instead of treating every available U as something to fill.

Network and power cables need defined routes that keep clear of airflow and do not make equipment difficult to remove. Fibre needs its own management to avoid excessive bending or accidental disturbance.

Cable entry comes from above or below depending on the facility. Know which before installation and you know where patch panels, switches and power distribution should sit.

Labelling matters too. A rack with clearly identified power feeds, network connections and equipment is easier to troubleshoot and safer to work on than one held together by memory and a bundle of indistinguishable cables.

The same goes for access. Confirm delivery procedures, loading arrangements and engineering access before equipment arrives. Rack dimensions are only useful if the hardware can reach them.

Colocation racks vs dedicated servers

Colocation and dedicated servers both give organisations access to physical infrastructure. The ownership and responsibility models are different.

Attribute Colocation Rack Dedicated Server
Hardware ownership Customer owns or controls the equipment Provider owns the server
Hardware choice Customer chooses the specification Limited to provider options
Rack and facility Operated by colocation provider Operated by hosting provider
Hardware maintenance Customer responsibility unless managed support is included Usually provider responsibility
Refresh cycle Customer decides when to replace equipment Provider manages available hardware options
Physical control High More limited
Scaling Requires additional hardware and capacity Additional servers ordered from provider

Colocation suits organisations that already own suitable equipment, or that want control over the hardware specification. Dedicated servers take away most of the hardware ownership responsibility and give you less control over the underlying platform.

What comes with colocation rack space?

A colocation rack is only useful because of the data centre infrastructure around it.

Physical security protects access to the facility and to the equipment inside it. Controls include monitored entry, CCTV, access management and locked cabinets or cages, depending on the site and service.

Resilient power can include A+B feeds alongside UPS systems, generators and redundant distribution paths.

Connectivity is another part of the environment. Carrier-neutral facilities give customers access to multiple network providers, so connectivity can be chosen based on geography, resilience, performance and commercial terms.

Monitoring and support matter once the equipment is live. Remote hands services let engineers at the facility carry out physical tasks such as checking equipment, rebooting a device, reseating a cable or replacing components when the customer’s own team is not on site.

At Datum, the rack sits within a wider service environment at Farnborough and Manchester. Carrier-neutral connectivity, service management and in-house engineering support sit alongside the power, cooling and physical security around the equipment.

The important thing is knowing where the provider’s responsibility ends and yours begins. Colocation gives you control over your hardware, which also means hardware maintenance, operating systems and applications stay yours unless the agreement includes managed services covering them.

Common colocation rack problems

Most rack problems start before the equipment reaches the data centre.

The first is ordering enough U space and not enough usable power. A cabinet sits there with empty slots and cannot support another server because the contracted power or cooling capacity has already been reached.

The second is checking height and ignoring depth. Deep servers, storage chassis and switches need clearance for cables and airflow. Equipment that technically fits between the rails can still be impractical to install or maintain.

Poor cable planning creates a different problem. Cables obstructing exhaust airflow undermine cooling, and badly labelled connections make routine changes and fault finding slower, with greater risk to service continuity.

Power resilience gets misunderstood too. Ordering A+B feeds only buys you diversity if the equipment is connected appropriately. A dual-PSU server uses separate feeds. Single-corded equipment needs a different arrangement to benefit from both paths.

Then there is access and support. Colocation does not mean your team turns up at any time and starts working outside the facility’s access procedures. Understand how visits are authorised, what remote hands can do and how chargeable engineering work is handled before you need any of it during an incident.

Finally, plan for growth. Fill the rack’s usable power allocation on day one and there is little room to add equipment later, whatever physical U is left.

Colocation rack pricing and options

Colocation rack pricing depends on more than cabinet size. A smaller deployment uses a quarter or half rack rather than paying for a complete cabinet. A full rack gives you the whole cabinet. Larger requirements expand across multiple racks, or into cages and dedicated areas.

Physical space is only one part of the quote. Power allocation can materially affect the price, particularly for higher-density equipment, and connectivity, cross-connects, installation work, remote hands and additional services can come as separate charges.

Location shapes the commercial model as well, and inside the UK that means more than mileage: racks in and around major tech hubs such as London and Manchester sit within a dense connectivity ecosystem, with access to major carriers and interconnection routes, while regional facilities may offer a different balance of connectivity, power availability, space and location. What matters is where your traffic needs to go and which services need to be within easy reach.

All of which makes headline rack prices hard to compare, across providers and across regions. A lower cabinet charge may come with a smaller power allocation or different connectivity and support costs. The more useful comparison is an itemised quote showing what’s included, what’s charged separately and how costs move if the deployment grows. The underlying facility is part of what you’re paying for as well: resilient electrical infrastructure, cooling systems, physical security, network availability and engineering teams all exist around the rack whether you occupy ten U or an entire suite. Compare the service around the cabinet, not the cost of the cabinet.

What to check before ordering colocation rack space

Build the requirement from the equipment upwards.

Check:

  • How many U does the equipment need now, and how much growth space is sensible?
  • What are the actual width and depth requirements?
  • How much usable power does the deployment need?
  • What power feeds and connectors does the equipment require?
  • Does the expected heat load fit the facility’s cooling design?
  • How will network and power cabling enter and move through the rack?
  • Which carriers and connectivity services are available?
  • Can resilient connections use genuinely separate paths?
  • How will equipment be delivered into the data hall?
  • What are the site access procedures?
  • What remote hands or engineering support is available?
  • Which charges are recurring, and which are one-off?
  • What changes if you need more power, space or connectivity later?

The best colocation rack specification is not the one that fits today’s equipment as tightly as possible. It is the one that gives the estate enough power, cooling, connectivity and physical room to run cleanly and absorb realistic change.

Talk to Datum about your colocation requirements

If you are planning a new colocation deployment or reviewing an existing rack requirement, talk to Datum about the space, power, connectivity and support your infrastructure needs. Farnborough serves London and the South East, while Manchester provides a strong northern platform for organisations building infrastructure in the North West and beyond.